日本TOYO数位式保护电驿Relay TDOG/TDOU,TDOG-31,TDOU-33,TDOG-31D,TDOU-33D 日本TOYO数位式保护电驿,TDOG-31,TDOU-33,TDOG-31D,TDOU-33D
产品简介
日本TOYO数位式保护电驿Relay TDOG/TDOU,日本TOYO数位式保护电驿,TDOG-31,TDOU-33,TDOG-31D,TDOU-33D昆山苏美自动化科技有限公司专业供应.
产品详细信息
TOYO-数位式保护电驿Relay TDOG/TDOU,日本TOYO数位式保护电驿Relay TDOG/TDOU,日本TOYO数位式保护电驿,TDOG-31,TDOU-33,TDOG-31D,TDOU-33D,昆山苏美自动化科技有限公司专业供应.
Time Setting & Curve
>95%
≤2.0 VA
12 VA
Vibration Resistance
(approx. 30G) 3 times each in 3 directios
TGOU - 33
(Fixed Type with RS485 output)
(Draw Out Type with RS485 output)
Rating
Input
AC 110A
Frequency
50/60 Hz ± 5%
Auxiliary Voltage
AC / DC 80~260V
Ambient Temperature
-10 ℃ / +60 ℃ (without icing)
Voltage Setting
[OV]
100 ~ 160V (1V step)
[UV]
50 ~ 120V (1V step)
Instantaneous
20 ~ 90V
Operating Value
100%(± 10% )
UV / OV Time Lever(tp)
Instantaneous Time
0.1~40(0.1 step)
<60ms
(Option:time adjustable version)
[OV]
V<95%
[UV]
V>105%
UV Inverse Time
OV Inverse Time
UV / OV Definite Time
t = tp
Resetting Value
Reset Time
< 100 ms
Operating Time
[OV]
Inverse or Definite Time
[UV]
Inverse or Definite Time
Burden
AC Voltage
AC Aux. Voltage
DC Aux. Voltage
6W
Comtact
Output Relay
Trip:1a
OV:1a UV:1a
Trip Contact Capacity
12A / 250VAC / 28VDC
Making Capacity
30A
Contact Material
Silver Alloy
Indicator (LED)
CPU State
(Self-diagnostic & monotoring)
Run (Green)
Communication Indication
COMM (Yellow)
Display Flicker when inputed OV / UV
AB,BC,CA / OV, UV (Red)
Fault phase / instantaneous
R.S.T.N / INST (Red)
Memory
Up to 10 records of fault data
RS 485 CommunicationParity
Protocol
Modbus
Comm. Speed
9600 / 19200 bps
Parity
None
Malfunction
10Hz 5mm double amplitude 30s each in X ans Y directions
16.7Hz 2.5mm double amplitude 600s each in X,Y,and Z directions
Shock Resistance
Destruction
Insulation
Dielectric Withstand
2KV for 1 minute between all terminals and case earth >1,000Ω
5KV-1.25/50μs
2.5KV 1MHz/200Ω < IEC255-6 > 2.2 KG
Enviromental & EMC Conditions
Dust & Drop Resistance
Front cover wuth IP42 protection level
Option:IP54 protection level
(with extra charge)