PERFORMANCE |
Measurement Range (RH) | 0-100% RH |
Measurement Range (T)-Configurable on Request | 0 to +50°C 0 to +100°C -20 to +80°C -30 to +20°C -30 to +70°C |
Accuracy RH @ 23°C | <±2% RH (5-95% RH) |
Accuracy T @ 23°C | Pt100 Ω 1/3 DIN direct ±0.2°C Current output ±0.3°C |
Stability - RH Sensor | <±1% RH/year |
Response Time | <10 sec typical (for 90% of the step change) |
ELECTRICAL INPUT/OUTPUT |
Output Signal (RH)-Configurable on Request | 4–20 mA 0–1 V, 0–5 V, 0–10 V |
Output Signal (T)-Configurable on Request | 4–20mA 3-wire 100 Ω 1/3 DIN direct Pt100 0–1 V, 0–5 V, 0–10 V |
Supply Voltage | Output 4–20mA: E = 12–30 VDC Output 0–10V: E = 15–30 VDC Output 0–5V: E = 10–30 VDC Output 0–1V: E = 8–30 VDC |
Load Resistance | Output 4–20mA: Rload < (Uv-9)/0.02 Output 0–10V: R > 10 k Ω Output 0–5V: R > 5 k Ω Output 0–1V: R > 1 k Ω |
Current Consumption | Analogue loops 2 x 20mA max |
OPERATING CONDITIONS |
Operating Temperature | Measurement head: -30 to +85°C Housing: -30 to +70°C Storage: -40 to +70°C |
Operating Humidity | Sensing element: 0–100% RH (non-condensing) Housing: 0–98% RH (non-condensing) Storage: 0–98% RH (non-condensing) |
MECHANICAL SPECIFICATIONS |
Ingress Protection Sensor | IP65 |
Housing Material | PPO |
Electrical Connections | Screw terminals, tightening torque 1.5mm2 max Output via wire to wire pitch from 3.5 to 6 mm diameter |
Dimensions | Housing: 80 x 80 x 34 mm Probe: L=85mm, ø12mm |
Weight | 100g |